487814_TA_100_C.jpg
The product is for outdoor use where a high level of protection against lightning and other climatic influences as well as mechanical stress is needed. A rare-gas-filled spark gap for the lightning protection equipotential bonding, the insulation of electrically separated parts and the bridging of insulating flanges of gas pipelines. Protection of power supply of dc.
  • Rare-gas-filled insulation spark gaps
  • High-quality industrial ceramics
  • Rare-gas filled, hermetically sealed
  • Free from radioactive substances
  • High discharge capacity up to 100 kA
  • Highly reliable, robust and waterproof
  • Extremely low sparkover voltage
  • Stable performance, long service life
  • Fail-safe characteristic
  • Test standard DIN EN 62561-3:2018-02
IEC category Class H
Nominal DC sparkover voltage at 100 V/sUagN 100 ±20% V=
Nominal AC sparkover voltage (50 Hz)Uaw 70 ±20% V
Typical impulse sparkover voltageUas 650 V
Max. impulse sparkover voltageUas 950 V
Lightning impulse current (10/350 µs) totalItotal 100 kA
Nominal impulse discharge current (10 x 8/20 µs)In 100 kA
5x Nominal alternating discharge current at 50 Hz, 1 s, 3 min pauseIwn 100/1 A/s
Nominal alternating discharge current (50 Hz) 200 / 0,5 A/s
Alternating current critical load (50 Hz) (1x 0.3s)Iwgr 4.000 / 0,25 Aeff/s
Additional Information
Spark-gap extinguishing conditionsVex <70V / <20A
Insulation resistance at 10 V, 100 V >1 GΩ
Self-capacitance at 1 kHz 9 pF
Test category/climatic category DIN IEC 60068-1 / 40/90/21
Relative humidity 10%...95% rh
Degree of protection IP 67
Operating temperature rangeTU -40 - + 80 °C
3x lightning impulse current (10/350 µs), long-duration current (CENELEC/BTTF 62-2)Iimp 75kA/38As/1,45MJ/Ω + 150A/0,5s/75As
20x lightning impulse current (10/45 µs) half-wave (DIN 48810) 60kA/ 10As/ 0,1 MJ /Ω
Terminals M8 bolt/nut (NIROSTA stainless steel)
Dimensions (Ø × L) ca. 59 x 99 mm
Total length with terminals ≤ 148 mm

Accessories

Related Products