Weather-resistant, moulded metal/ceramic isolating spark gap with terminal lugs for M8 screw connection. Waterproof moulded in polyurethan diecast. A rare-gas-filled spark gap for the lightning protection equipotential bonding, the insulation of electrically separated parts and the bridging of insulating flanges of gas pipelines. Protection of power supply of dc.
  • Gasfilled spark gap (TS)
  • High-quality industrial ceramics
  • Rare-gas filled, hermetically sealed
  • Free from radioactive substances
  • High lightning current discharge capacity of 100 kA (10/350 µs) (class H)
  • Extremely low sparkover voltage
  • Highly reliable, robust and waterproof
  • Fail-safe characteristic
  • Stable performance, long service life
  • Test standard DIN EN 62561-3:2018-02
IEC category Class H
Nominal DC sparkover voltage at 100 V/sUagN 500 ±15% V=
Nominal AC sparkover voltage (50 Hz)Uaw 350 ±15% V
Typical impulse sparkover voltageUas 950 V
Max. impulse sparkover voltageUas 1300 V
Lightning impulse current (10/350 µs) totalItotal 100 kA
Nominal impulse discharge current (10 x 8/20 µs)In 100 kA
5x Nominal alternating discharge current at 50 Hz, 1 s, 3 min pauseIwn 100/1 A/s
Nominal alternating discharge current (50 Hz) 200 / 0,5 A/s
Alternating current critical load (50 Hz) (1x 0.3s)Iwgr 4.000 / 0,25 Aeff/s
Additional Information
Spark-gap extinguishing conditionsVex < 230V/< 100A
Insulation resistance at 10 V, 100 V >1 GΩ
Self-capacitance at 1 kHz 7 pF
Test category/climatic category DIN IEC 60068-1 / 40/90/21
Relative humidity 10%...95% rh
Degree of protection IP 67
Operating temperature rangeTU -40 - +80 °C
3x lightning impulse current (10/350 µs), long-duration current (CENELEC/BTTF 62-2)Iimp 75 kA / 38 As/1,45 MJ/Ω + 150 A / 0,5 s / 75 As
20x lightning impulse current (10/45 µs) half-wave (DIN 48810) 60 kA/10 As/0,1 MJ/Ω
Terminals Hole 8,5 mm copper, nickelplate
Dimensions (Ø × L) ca. 50 x 86 mm
Total length with terminals ≤ 138 mm