Waterproof isolating spark-gap for underground installation (soil). Moulded in PU diecast, with cables. A rare-gas-filled spark gap for the lightning protection equipotential bonding, the insulation of electrically separated parts and the bridging of insulating flanges of gas pipelines.
- Gasfilled spark gap (TS)
- High-quality industrial ceramics
- Rare-gas filled, hermetically sealed
- Free from radioactive substances
- High discharge capacity up to 100 kA
- Extremely low sparkover voltage
- Highly reliable, stable functioning
- Fail-safe characteristic
- SNAM execution
- Test standard DIN EN 62561-3:2018-02
- Including 2m connection cables with 25mm²
IEC category | Class H |
Nominal DC sparkover voltage at 100 V/sUagN | 100 ±20% V= |
Nominal AC sparkover voltage (50 Hz)Uaw | 70 ±20% V |
Typical impulse sparkover voltageUas | 650 V |
Max. impulse sparkover voltageUas | 950 V |
Nominal impulse discharge current (10 x 8/20 µs)In | 100 kA |
Lightning impulse current (10/350 µs) totalItotal | 100 kA |
3x lightning impulse current (10/350 µs), long-duration current (CENELEC/BTTF 62-2)Iimp | 75 kA/38 As/1,45 MJ/Ω plus 150 A / 0,5s /75As |
20x lightning impulse current (10/45 µs) half-wave (DIN 48810) | 60 kA/10As/0,1 MJ/Ω |
5x Nominal alternating discharge current at 50 Hz, 1 s, 3 min pauseIwn | 100/1 A/s |
Additional Information
Nominal alternating discharge current (50 Hz) | 200 / 0,5 A/s |
Alternating current critical load (50 Hz) (1x 0.3s)Iwgr | 4.000 / 0,25 Aeff/s |
Spark-gap extinguishing conditionsVex | < 70V / <20A |
Insulation resistance at 10 V, 100 V | >1 GΩ |
Self-capacitance at 1 kHz | 9 pF |
Test category/climatic category | DIN IEC 60068-1 / 40/90/21 |
Relative humidity | 10%...95% rh |
Degree of protection | IP 67 |
Operating temperature rangeTU | -40 - +80 °C |
Terminals | Cabel 2m/ 25 mm² |
Dimensions (Ø × L) | 70 x 340 mm |
Total length with terminals | ≤ 4340 mm |