Surge protection for equipment and installations up to 100 A and 150 V.
- Surge Protective Device type 2, class II
- High performance arrester for 150 V operating voltage
- Function control indication via LED
- Signalling contact (break contact) with pluggable terminal (Pk)
- EAC certification
IEC category | Type 2 + 3 / class II + III |
Nominal voltage DCUN | 150 V= |
Nominal voltage ACUN | 120 V~ |
Max. continuous operating voltage AC (50/60 Hz) Uc | 170 V~ |
Protection levelUp | ≤ 1,0 kV |
Lightning impulse current (10/350 µs)Iimp | 8 kA |
Max. impulse discharge current (8/20 µs)Imax | 40 kA |
Max. allowed fuse or back-up fuse | 125 A gG |
Response timetA | ≤ 25 ns |
Max. conductor cross section | 50 mm² single wire / 35 mm² stranded / 25 mm² fine-stranded with sleeve |
Additional Information
Max. connection torque for terminals | 1,5 Nm |
Operating temperature rangeTU | -40 - +80 °C |
Degree of protection (IEC EN 60529) | IP 20 |
Enclosure material / colour | polycarbonate (halogen-free) UL 94-V0 / yellow |
Mounting on | 35 mm DIN rail (EN 60715) |
Max. conductor cross section Pk | 1,5 mm² |
Max. current carrying capacity PK | 250 V/2 A |
Power supply system | 1 phase TN systems |