373930_PP_BCD_TT_25-100_v03.jpg
The installation place of the PowerPro BCD is the main distribution board upstream or downstream of the power meter. According to the lightning protection zones concept in IEC DIN EN 62305 part 1-4 (VDE 0185-305-1-4), it can universally be installed at the transition 0A to 2. Combined four-pole arrester for 3-phase TT and TN-S systems.
  • Remote signalling contact: break contact
  • Combined Arresters Class I+II+III (T1+T2+T3)
  • Test standard: IEC 61643-11 / EN 61643-11
  • No leakage currents, thus, allowing installation upstream of power meters
  • Rare-gas-filled spark gap, hermetically sealed
  • 4-pole; 3+1 N-PE
  • EAC certification
IEC category Type 1 + 2 + 3 / class I+II+III
Nominal voltage ACUN 230/400 V~
Max. continuous operating voltage AC (50/60 Hz) Uc 255 V~
Insulation resistanceRisol > 10 GΩ
Protection level at 100% lightn. imp. sparkover voltage (1.2/50µs)Up ≤ 1,0 kV
Protection levelUp ≤ 1,0 kV
Response timetA < 50 ns
Lightning impulse current (10/350 µs) totalItotal 100 kA
Lightning impulse current (10/350 µs) L-N/N-PE/L-PENIimp 25 / 100 / - kA
Follow-on current extinguishing capability at Uc (50/60 Hz)Ifi 4,0 kA
Additional Information
Short-circuit withstand capability at max. back-up fuseISCCR 50 kAeff
Max. acceptable back-up fuse F2 (spur wiring) 250 A gG
Max. acceptable back-up fuse F1 (serial wiring) 125 A gG
Operating temperature rangeTU -40 - +80 °C
Max. conductor cross section 50 mm² stranded/35 mm² flexible
Recommended conductor cross section 25 mm²
Max. connection torque for terminals 4,0 Nm
Enclosure material / colour polycarbonate (halogen-free) UL 94-V0 / yellow
FM contact / contact type break contact
Switching capacity FM 250 V/2 A
Max. conductor cross section FM 1,5 mm²
Max. locking torque FM terminals 0,25 Nm
Degree of protection (IEC EN 60529) IP 20
Mounting on 35 mm DIN rail (DIN EN 60715 )
Dimension (DIN 43880) 8 TE
Power supply system 3 phase TT systems