EPS T1+2/4+0-320-12.5-FM
Article Nr. : 380703
Four pole pluggable combined lightning and surge arrester, for example for 3-phase TN-S systems. Mechanical status indicator: State of the surge protective device is optically indicated.
- Combined Arresters Type 1+2 (Class I+II)
- Test standard: IEC 61643-11 / EN 61643-11
- High lightning impulse discharge current of 12.5 kA (10/350 µs) per pole
- Mechanical status indicator: State of the surge protective device is optically indicated.
- Place of installation: main distributer
- Remote changeover contact (FM)
IEC category | Type 1 + 2 / class I+II |
Nominal voltage ACUN | 240 V~ |
Max. continuous operating voltage AC (50/60 Hz) Uc | 320 V~ |
Nominal discharge current (8/20 µs) L-N/N-PE/L-PENIn | 25 / - / - kA |
Max. discharge current (8/20 µs) L-N/N-PE/L-PENImax | 50 / - / - kA |
Lightning impulse current (10/350 µs) L-N/N-PE/L-PENIimp | 12,5 / - / - kA |
Specific Energy W/R | 39 kJ/Ω |
ChargeQ | 6,25 As |
Protection levelUp | < 1,5 kV |
Response timetA | < 25 ns |
Additional Information
Max. allowed fuse or back-up fuse | 250 A gG |
Short-circuit withstand capability at max. back-up fuseISCCR | 25/50 kAeff |
TOV withstand 5sUT | 337 V |
Temporary overvoltage rating 120 minUT | 442 V |
Operating temperature rangeTU | -40 - +85 °C |
Max. conductor cross section | stranded 35/fine stranded 25 mm² |
Max. connection torque for terminals | 4,5 Nm |
Degree of protection (IEC EN 60529) | IP 20 |
Enclosure material / colour | Thermoplastic: Extinguishing Degree UL 94 V-0/grey |
Dimension (DIN 43880) | 4 TE |
Mounting on | 35 mm DIN rail (DIN EN 60715 ) |
FM contact / contact type | changeover contact |
Max. conductor cross section FM | 1,5 mm² |
Switching capacity FM | AC: 250V, 125V:1A / DC: 48V, 24V, 12V: 0,5A |
Power supply system | 3 phase TNS systems |
Dimension (DIN 43880) | 4 TE |
Dimensions (L x W x H) | 80,5 x 90 x 72 mm |