LT ZP ST T1+2+3/3+1-275-12.5kA

Article Nr. : 381681

381681_LT ZP ST T1+2+3_3+1-275-12.5kA_v02.jpg
Four pole pluggable combined lightning and surge arrester, for example for 3-phase TT and TN-S systems. Location of use: Main distribution boards, 40mm busbar systems For buildings with external lightning protection (lightning protection class III / IV). Can be used for lightning protection classes III and IV.
  • 40mm busbar SPD
  • Combined Arresters Class I+II+III (T1+T2+T3)
  • Test standard: IEC 61643-11 / EN 61643-11
  • Leakage current-free
  • Visual function indicator
  • On the basis of hermetically sealed rare-gas-filled spark gaps
IEC category Type 1 + 2 + 3 / class I+II+III
Nominal voltage ACUN 230/400 V~
Max. continuous operating voltage AC (50/60 Hz) Uc 275 V~
Nominal discharge current (8/20 µs) L-N/N-PE/L-PENIn 20 / k.A. / - kA
Max. discharge current (8/20 µs) L-N/N-PE/L-PENImax 50 / k.A. / - kA
Lightning impulse current (10/350 µs) L-N/N-PE/L-PENIimp 12,5 / 50 / - kA
Combined surgeUoc 6 kV
Protection level at In (8/20 µs)Up 1,0 kV
Protection level at In (8/20 µs) (L-N)Up 1,25 kV
Protection level L-PE at In (8/20 µs)Up 1,5 kV
Additional Information
Specific Energy W/R 40 kJ/Ω
Max. acceptable fuse or back-up fuse 315 A gG
Short-circuit withstand capability at max. back-up fuseISCCR 50 kAeff
TOV withstand 5sUT 335 V
Temporary overvoltage rating 120 minUT 440 V
Temporary overvoltage rating 200ms N-PEUT 1200 V / 300 A / 200 ms V
Operating temperature rangeTU -40 - +85 °C
Max. connection torque for terminals 3,5 - 4 (PZ-2) Nm
Max. conductor cross section 35 mm² stranded/25 mm² flexible
Mounting 40mm busbar systems
Degree of protection (IEC EN 60529) IP 20
Enclosure material / colour Thermoplastic UL 94-V0/yellow
Power supply system 3 phase TNS and TT systems
Installation dimensions (H × W × D) 211 × 95 × 53,8 mm