Generator connection box for three phase TNS system. Application: e. g. at PV systems to protect the AC side of the inverter.
  • With remote signalling contact (FM)
  • Protection of inverter rectifier AC-side
  • Housing of surface mounting (300 x 200 x 132 mm) is UV resistant
  • Four pole SPD PP BC TNS 25/100
IEC category Type 1 + 2 / class I+II
Cross section for E-termials (entry) 16 mm²
Cross section for A-terminals (exit) single wire / stranded 16 mm²
Cable feedthrough 2x M25/1x M20
Degree of protection (IEC EN 60529) IP 66
Dimensions (L x W x H) 300 x 200 x 132 mm
Operating temperature rangeTU -40 - +80 °C
Nominal voltage ACUN 230/400 V~
Max. continuous operating voltage AC (50/60 Hz) Uc 255 V~
Insulation resistanceRisol > 10 GΩ
Additional Information
Protection level at 100% lightn. imp. sparkover voltage (1.2/50µs)Up ≤ 2,5 kV
Protection level at Iimp L-PEUp ≤ 2,5 kV
Lightning impulse current (10/350) L1+L2+L3+N-PEItotal 100 kA
Lightning impulse current (10/350) L,N-PEIimp 25 kA
Follow-on current extinguishing capability at Uc (50/60 Hz)Ifi 4 kA
Short-circuit withstand capability at max. back-up fuseISCCR 50 kAeff
Max. acceptable back-up fuse F2 (spur wiring) 250 A gG
Max. acceptable back-up fuse F1 (serial wiring) 125 A gG
Max. conductor cross section stranded 50/fine stranded 35 mm²
Recommended conductor cross section 25 mm²
Max. connection torque for terminals 4,0 Nm