PP PV 1000-12,5kA-FM
Article Nr. : 374405
When applied in PV installations, these devices are placed inside the connection box of the solar generator and on the DC side of the inverter.
- DC Combined Arrester Type 1+2
- Two-pole combined lightning current and surge arrester dc, type 1 + type 2
- Applicable at the LPZ transition point 0A-1 and higher
- Test standard: IEC 61643-11 / EN 61643-11
- Space required for installation: 54 mm
- Mounting on 35 mm DIN rail (EN 60715)
- EAC certification
IEC category | Type 1 + 2 / class I+II |
PV voltageUocSTC | 1000 V= |
Max. continuous operating voltage DCUc | 1100 V= |
Protection level at In (8/20 µs)Up | ≤ 4,2 kV |
Protection level at 5 kAUp | ≤ 3.5 kV |
Response timetA | ≤ 25 ns |
Lightning impulse current (10/350 µs)Iimp | 6 kA |
Lightning impulse current (10/350 µs) totalItotal | 12,5 kA |
Max. impulse discharge current (8/20 µs)Imax | 20 kA |
Operating temperature rangeTU | -40 - +80 °C |
Additional Information
Min. conductor cross section at terminals | 10 mm² |
Max. conductor cross section | 35 mm² stranded/25 mm² flexible |
Max. connection torque for terminals | 4,0 Nm |
Enclosure material / colour | polycarbonate (halogen-free) UL 94-V0 / yellow |
Degree of protection (IEC EN 60529) | IP 20 |
Dimension (DIN 43880) | 3 TE |
FM contact / contact type | break contact |
Max. conductor cross section FM | 1,5 mm² |
Switching capacity FM | 250 V/2 A |
Max. locking torque FM terminals | 0,25 Nm |
Recommended conductor cross section | 25 mm² |
Mounting on | 35 mm DIN rail (EN 60715) |