DP 2x1-12V/12V-Tr
Article Nr. : 271212-A
EMC filter for data and signal lines combined with surge protection enables smooth operation of sensitive electronic equipment in rough environment.
- Signal and data line protection with low-pass filter
- Signal and data line protection with low-pass filter
- Protective circuit for 2 signal lines with common ground
- Applicable at the boundaries LPZ 0A - 2 and higher
- Mounting on 35 mm DIN rail (EN 60715)
- Degree of protection according to IEC EN 60529: IP 20
- Space required for installation: 18 mm
- EAC certification
IEC category | D1 / C2 / C1 / C3 |
Nominal voltage DCUN | 12 V= |
Max. continuous operating voltage DCUc | 13,6 V= |
Max. continuous operating voltage AC (50/60 Hz) Uc | 10 V~ |
Nominal currentIL | 0,4 A |
D1 lightning impulse current (10/350 µs) per lineIimp | 2,5 kA |
D1 lightning impulse current (10/350 µs) totalItotal | 5 kA |
C2 nominal discharge current (8/20 µs) per lineIn | 10 kA |
C2 nominal discharge current (8/20 µs) totalImax | 20 kA |
Protection level at In (line-earth)Up | ≤ 18 V |
Additional Information
Leakage current at Uc | ≤ 5 µA |
DC resistanceR | 3,2 Ω |
Series inductance, typ.L | 30 µH |
Response timetA | ≤ 2 ns |
Capacitance, line-earthC | <2,3 nF |
Max. operating frequency (-3 dB)fG | 600 kHz |
Operating temperature rangeTU | -25 - +85 °C |
Max. conductor cross section | 2.5mm² solid or 1.5mm² flexible with sleeve |
Max. connection torque for terminals | 1,5 Nm |
Enclosure material / colour | polycarbonate (halogen-free) UL 94-V0 / yellow |
Degree of protection (IEC EN 60529) | IP 20 |
Dimension (DIN 43880) | 1 TE |
Mounting on | 35 mm DIN rail (DIN EN 60715 ) |