They provide extremely high discharge capacity with at the same time very low protection levels and they also do not need any damageable internal or external electronic trigger. Combined arrester with rare-gas-filled spark gap and very low protection level < 1.0 kV. Connection boxes in the pre-counter section for the use in 3 phase TT or TNS sytems according to DIN VDE 0100-443 und -534. Application in the non-measured area in front of energy meter only after consulting of the power network operator.
  • Connectiion boxes wit SPD type 1 + 2 + 3
  • Applicable at the boundaries LPZ 0A - 2
  • Test standard: IEC 61643-11 / EN 61643-11
  • Degree of protection according to IEC EN 60529: IP 66
  • Inflammability class according to UL 94 V0
  • Remote changeover contact (FM)
  • no leackage current
  • Single modules can be replaced easily
  • Sealable
IEC category Type 1 + 2 + 3 / class I+II+III
Nominal voltage ACUN 230/400 V~
Max. continuous operating voltage AC (50/60 Hz) Uc 350 V~
Lightning impulse current (10/350 µs) totalItotal 100 kA
Lightning impulse current (10/350 µs) L-N/N-PE/L-PENIimp 25 / 100 / - kA
Nominal discharge current (8/20 µs) L-N/N-PE/L-PENIn 25 / 100 / - kA
Protection levelUp ≤ 1,0 kV
Follow-on current extinguishing capability AC L-N (260 V AC) Ifi 4,0 kAeff
Follow-on current extinguishing capability AC N-PEIfi 100 Aeff
Short-circuit withstand capability at max. back-up fuseISCCR 50 kAeff
Additional Information
Max. acceptable backup fuse (V-type through wiring) 125 A gG
Operating temperature rangeTU -40 - +80 °C
Min. conductor cross section at terminals 10 mm² solid/flexible
Max. conductor cross section 50 mm² stranded/35 mm² flexible
Max. connection torque for terminals 4,0 Nm
Max. operating voltage remote contact FM 250 V AC/125 V DC
Max. operating current remote contact FM 1 A AC/200 mA DC
Max. conductor cross section FM 1,5 mm²
Max. locking torque FM terminals 0,25 Nm
Dimensions of housing (H × W × D) 300 x 300 x 132 mm
Cable feedthrough 2x M50
Power supply system 3 phase TNS and TT systems