Lightning current discharge arrester (class I) with rare-gas-filled spark gap for the use in three-phase TT and TN-S systems. They provide extremely high discharge capacity with at the same time very low protection levels and they also do not need any damageable internal or external electronic trigger. Connection boxes in the pre-counter section for the use in 3 phase TT or TNS sytems according to DIN VDE 0100-443 und -534. Application in the non-measured area in front of energy meter only after consulting of the power network operator.
- Connection Boxes with SPD Type 1
- Applicable at the boundaries LPZ 0A - 1
- Test standard: IEC 61643-11 / EN 61643-11
- Remote changeover contact (FM)
- Inflammability class according to UL 94 V0
- no leackage current
- Optical status indication (red pin appears)
- Degree of protection according to IEC EN 60529: IP 66
- Single modules can be replaced easily
- Sealable
IEC category | Type 1 / class I |
Nominal voltage ACUN | 230/400 V~ |
Max. continuous operating voltage AC (50/60 Hz) Uc | 350 V~ |
Lightning impulse current (10/350 µs) totalItotal | 100 kA |
Lightning impulse current (10/350 µs) L-N/N-PE/L-PENIimp | 25 / 100 / - kA |
Nominal discharge current (8/20 µs) L-N/N-PE/L-PENIn | 25 / 100 / - kA |
Protection levelUp | ≤ 2,5 kV |
Follow-on current extinguishing capability AC L-N (260 V AC) Ifi | 10 kAeff |
Follow-on current extinguishing capability AC N-PEIfi | 100 Aeff |
Short-circuit withstand capability at max. back-up fuseISCCR | 50 kAeff |
Additional Information
Max. acceptable backup fuse (V-type through wiring) | 125 A gG |
Operating temperature rangeTU | -40 - +80 °C |
Min. conductor cross section at terminals | 10 mm² solid/flexible |
Max. conductor cross section | 50 mm² stranded/35 mm² flexible |
Max. conductor cross section FM | 1,5 mm² |
Max. connection torque for terminals | 4,0 Nm |
Inflammability class according to UL 94 | V0 |
Max. operating voltage remote contact FM | 250 V AC/125 V DC |
Max. operating current remote contact FM | 1 A AC/200 mA DC |
Max. locking torque FM terminals | 0,25 Nm |
Dimensions of housing (H × W × D) | 300 x 300 x 132 mm |
Cable feedthrough | 2x M50 |
Power supply system | 3 phase TNS and TT systems |