Compact and leakage-current free 1-pole surge arrester class II for nominal voltage DC of 220 V and rated load current of 16 A.
  • SPD type 2 for DC power supplies
  • Remote signalling contact: break contact
  • Practical compact housing with minimum space requirement
  • Leackage current free
IEC category Type 2 /class II
Nominal voltage DCUN 220 V=
Max. continuous operating voltage DCUc 230 V=
Rated load currentIL 16 A
Protection level at In (8/20 µs)Up ≤ 1,5 kV
Response time +/- to PENtA ≤ 100 ns
Nominal impulse discharge current (10 x 8/20 µs)In 20 kA
Max. impulse discharge current (8/20 µs)Imax 25 kA
Max. allowed fuse or back-up fuse 16 A gG
Operating temperature rangeTU -40 - +80 °C
Additional Information
Min. conductor cross section at terminals 2.5 mm² single-wire / 1.5 mm² flexible with sleeve
Max. conductor cross section 2.5 mm² flexible / 4mm² solid
Enclosure material / colour polycarbonate (halogen-free) UL 94-V0 / yellow
Degree of protection (IEC EN 60529) IP 20
Mounting on 35 mm DIN rail (DIN EN 60715 )
FM contact / contact type break contact
Switching capacity FM 250 V/2 A
Max. conductor cross section FM 1.5 mm² solid/flexible mm²