The SPD is applicable at the transition 2-3 according to the lightning protection zones concept. Pluggable 2-pole surge arrester type 3 (class III) for TN systems.
- Surge voltage protector (class III T3 )
- Test standard: IEC 61643-11 / EN 61643-11
- Line function and equipment control by LED
- Leackage current free
- Remote signalling contact: break contact
- Housing width: 17.5 mm
- Shock test standard: DIN EN 60068-2-27, IEC 60068-2-27
- Vibration test standard: DIN EN 60068-2-6, IEC 60068-2-6
- EAC certification
IEC category | Type 3 / class III |
Nominal voltage ACUN | 60 V~ |
Max. continuous operating voltage AC (50/60 Hz) Uc | 75 V~ |
Rated load currentIL | 16 A |
Protection level L-NUp | ≤ 0,5 kV |
Protection level L/N-PEUp | ≤ 1,0 kV |
Combined surgeUoc | ≤ 2 kV |
Response time L-N/L,N-PE | ≤ 25/≤ 100 ns |
Nominal impulse discharge current (10 x 8/20 µs)In | 5 kA |
Max. impulse discharge current (8/20 µs)Imax | 8 kA |
Additional Information
Max. allowed fuse or back-up fuse | 16 A gG |
Operating temperature rangeTU | -40 – +80 °C |
Conductor cross section (solid/stranded/AWG) | 0.2-4.0/0.2-2.5 mm² / 24-12 |
Enclosure material / colour | Thermoplastic, yellow/black, UL 97 V-0 |
Degree of protection (IEC EN 60529) | IP 20 |
Mounting on | 35 mm DIN rail (EN 60715) |
FM contact / contact type | break contact |
Switching capacity FM | 250 V/2 A |
Max. conductor cross section FM | 0.2-4.0/0.2-2.5 mm² / 24-12 mm² |
Max. locking torque FM terminals | 0,4 Nm |
Power supply system | 1 phase TN systems |