373815_IP B 25_v03.jpg
Single pole SPD type 1 for use as equipotential bonding lightning surge protection in different kind of power net systems. Lightning current discharge arrester (class I) with rare-gas-filled spark gap for the use in single-phase TT and TN systems. Applicable at the boundaries LPZ 0A - 1 and higher.
  • Lightning current arresters type 1 (class I)
  • Test standard: IEC 61643-11 / EN 61643-11
  • Rare-gas-filled spark gap, hermetically sealed
  • Applicable at the boundaries LPZ 0A - 1 and higher.
  • No leakage currents, thus, allowing installation upstream of power meters
  • High insulation resistance
  • All-in-one protection unit, ready for connection
  • Mounting on 35 mm DIN rail (EN 60715)
  • Degree of protection according to IEC EN 60529: IP 20
  • Inflammability class according to UL 94 V0
  • EAC certification
  • Remote signalling contact: break contact
  • Switching capacity FM: 205 V /2 A
  • Max. conductor cross section FM: 1.5 mm²
IEC category Type 1 / class I
Nominal voltage ACUN 230/400 V~
Max. continuous operating voltage AC (50/60 Hz) Uc 255 V~
Insulation resistanceRisol > 10 GΩ
Protection level at 100% lightn. imp. sparkover voltage (1.2/50µs)Up ≤ 4,0 kV
Protection levelUp ≤ 4,0 kV
Response timetA < 50 ns
Lightning impulse current (10/350 µs) totalItotal 25 kA
Lightning impulse current (10/350 µs) L-N/N-PE/L-PENIimp 25 / - / - (L,N-PE) kA
Short-circuit withstand capability at max. back-up fuseISCCR 50 kAeff
Additional Information
Max. acceptable back-up fuse F2 (spur wiring) 160 A gG
Max. acceptable back-up fuse F1 (serial wiring) 125 A gG
Operating temperature rangeTU -40 - +80 °C
Max. conductor cross section 50 mm² stranded/35 mm² flexible
Recommended conductor cross section 25 mm²
Max. connection torque for terminals 4,0 Nm
Enclosure material / colour polycarbonate (halogen-free) UL 94-V0 / yellow
Degree of protection (IEC EN 60529) IP 20
Mounting on 35 mm DIN rail (EN 60715)
Power supply system between L and N
Max. switching capacity of remote signal contact 250 /2 V/A
Max. conductor cross section FM 1,5 mm²
Max. locking torque FM terminals 0,25 Nm
Min. conductor cross section at terminals 10 mm²
Dimension (DIN 43880) 2 TE