PowerPro B-Tr/50kA/Pk
Article Nr. : 373840
Single-pole lightning and transient (switching-) surge voltage arrester for the protection of low-voltage electrical distribution systems by industrial, commercial and private use.
- Signalling contact (break contact) with pluggable terminal (Pk)
- Lightning current arresters type 1 (class I)
- Test standard: IEC 61643-11 / EN 61643-11
- EAC certification
IEC category | Type 1 / class I |
Nominal voltage ACUN | 230/400 V~ |
Nominal voltage DCUN | > 800 V= |
Max. continuous operating voltage AC (50/60 Hz) Uc | 255 V~ |
Insulation resistanceRisol | > 10 GΩ |
Protection level at 100% lightn. imp. sparkover voltage (1.2/50µs)Up | ≤ 4.0 kV |
Protection levelUp | ≤ 4,0 kV |
Response timetA | < 50 ns |
Lightning impulse current (10/350 µs) totalItotal | 50 kA |
Lightning impulse current (10/350 µs) L-N/N-PE/L-PENIimp | 50 / - / - kA |
Additional Information
Follow-on current extinguishing capability at Uc (50/60 Hz)Ifi | 4 kA |
Short-circuit withstand capability at max. back-up fuseISCCR | 4,0 kAeff |
Max. acceptable back-up fuse F2 (spur wiring) | 250 A gG |
Max. acceptable back-up fuse F1 (serial wiring) | 125 A gG |
Operating temperature rangeTU | -40 - +80 °C |
Max. conductor cross section | 50 mm² stranded/35 mm² flexible |
Recommended conductor cross section | 25 mm² |
Max. connection torque for terminals | 4,0 Nm |
Enclosure material / colour |