373858_PP BCD 27kA-350_v03.jpg
Single-pole lightning and transient (switching-) surge voltage arrester for the protection of low-voltage electrical distribution systems by industrial, commercial and private use. Single-pole SPDs are used in 1-phase TN networks, where the N conductor does not have to be protected.
  • Remote signalling contact: break contact
  • Combined Arresters Class I+II+III (T1+T2+T3)
  • Test standard: IEC 61643-11 / EN 61643-11
  • Combined Arresters Class I+II+III (T1+T2+T3)
  • No leakage currents, thus, allowing installation upstream of power meters
  • Rare-gas-filled spark gap, hermetically sealed
  • Applicable at the boundaries LPZ 0A - 1 and higher.
  • 35 mm DIN rail (EN 60715)
  • EAC certification
IEC category Type 1 + 2 + 3 / class I+II+III
Nominal voltageUN 230/400 V
Max. continuous operating voltage AC (50/60 Hz) Uc 350 V~
Insulation resistanceRisol > 10 GΩ
Protection level at 100% lightn. imp. sparkover voltage (1.2/50µs)Up ≤ 1.0 kV
Protection levelUp ≤ 1.0 kV
Response timetA < 50 ns
Lightning impulse current (10/350 µs)Iimp 27 kA
Max. impulse discharge current (8/20 µs)Imax 80 kA
Follow-on current extinguishing capability at Uc (50/60 Hz)Ifi 4.0 kA
Additional Information
Short-circuit withstand capability at max. back-up fuseISCCR 25 kAeff
Max. acceptable back-up fuse F2 (spur wiring) 250 A gG
Max. acceptable back-up fuse F1 (serial wiring) 125 A gG
Operating temperature rangeTU -40 – +80 °C
Max. conductor cross section 50 mm² stranded/35 mm² flexible
Recommended conductor cross section 25 mm²
Max. connection torque for terminals 4,0 Nm
Enclosure material / colour polycarbonate (halogen-free) UL 94-V0 / yellow
Degree of protection (IEC EN 60529) IP 20
Mounting on 35 mm DIN rail (DIN EN 60715 )
Switching capacity FM 250 V/2 A
Max. conductor cross section FM 1,5 mm²
Max. locking torque FM terminals 0,25 Nm
Power supply system between L and PE
Dimension (DIN 43880) 2 TE