374504_PP BC TNC_50_400_690_v02.jpg
For lightning protection equipotential bonding in 400 V TN-C systems e. g. Wind generator protection
  • Protection of Wind Energy Systems
  • Test standard: IEC 61643-11 / EN 61643-11
  • Three pole combined arrester
  • For 440/690 V power system voltages
  • Low protection level
  • Optional remote signalling contact (FM)
  • Remote signalling contact: break contact
  • EAC certification
IEC category Type 1 + 2 / class I+II
Nominal voltage ACUN 400/690 V~
Max. continuous operating voltage AC (50/60 Hz) Uc 440 V~
Insulation resistanceRisol > 10 GΩ
Protection level at 100% lightn. imp. sparkover voltage (1.2/50µs)Up ≤ 2.5 kV
Protection levelUp ≤ 2.5 kV
Response timetA 100 ns
Lightning impulse current (10/350 µs) totalItotal 150 kA
Lightning impulse current (10/350 µs) L-N/N-PE/L-PENIimp - / - / 50 kA
Follow-on current extinguishing capability at Uc (50/60 Hz)Ifi 10 kA
Additional Information
Short-circuit withstand capability at max. back-up fuseISCCR 50 kAeff
Max. acceptable back-up fuse F2 (spur wiring) 250 A gG
Max. acceptable back-up fuse F1 (serial wiring) 125 A gG
Operating temperature rangeTU -40 - +80 °C
Max. conductor cross section 50 mm² stranded/35 mm² flexible
Recommended conductor cross section 25 mm²
Max. connection torque for terminals 4,0 Nm
Enclosure material / colour polycarbonate (halogen-free) UL 94-V0 / yellow
FM contact / contact type break contact
Switching capacity FM 250 V/2 A
Max. locking torque FM terminals 0,25 Nm
Degree of protection (IEC EN 60529) IP 20
Mounting on 35 mm DIN rail (DIN EN 60715 )
Power supply system 3 phase TNC systems
Dimension (DIN 43880) 6 TE