382042_EnerPro284Tr-M_v02.jpg
Four-pole, compact surge arrester e.g. for 3-phase TT systems.
  • Surge Protective Device type 2, class II
  • Function control indication via LED
  • No blow-out vents, thus, not requiring any safety clearance to other installations
  • EAC certification
IEC category Type 2 /class II
Nominal voltage DCUN 500 (N-PE) V=
Nominal voltage ACUN 230/400 V~
Max. continuous operating voltage AC (50/60 Hz) Uc 275 V~
Insulation resistanceRisol ≥ 10 GΩ
Impulse sparkover voltage (1.2/50 μs)Uas ≤ 1,4 (N/PE ≤1,5) kV
Response time 10 kV/µstA <5 ns
Protection level at 5 kA (8/20 µs)Up ≤ 0,8 kV
Nominal discharge current (8/20 µs)In 10x 15 kA
Max. impulse discharge current (8/20 µs)Imax 1x 40 kA
Additional Information
Lightning impulse current (10/350 µs) N-PEIimp 12 kA
Max. acceptable fuse or back-up fuse 125 A gG
Short-circuit current extinguishing capacity line-earth 100 A
Operating temperature rangeTU -40 - +80 °C
Max. conductor cross section 50 mm² stranded/35 mm² flexible
Recommended conductor cross section 25 mm²
Max. connection torque for terminals 4,0 Nm
Enclosure material / colour polycarbonate (halogen-free) UL 94-V0 / yellow
Degree of protection (IEC EN 60529) IP 20
Mounting on 35 mm DIN rail (EN 60715)
Switching capacity FM 250 V/2 A
Max. conductor cross section Pk 1.5 mm²
Power supply system 3 phase TNS and TT systems