The surge protection magazines of series MTH and MTL are fitted with high quality gas discharge tubes. The are avaibable in variations of 90 V ac and 230 V ac executions. They are designed specially for HVT 71 application of Siemens main distribution in telecom and datat line systems. The integrated fail-safe behaviour protects against dangerous ac influences.
- Fitted magazines for HVT 71
- Magazines are fitted with 10 gas-filled surge arrester (GDT) each
- Stable performance, long service life
- For 5 double lines
Nominal DC sparkover voltage at 100 V/sUagN | 90 V= |
Tolerance of VsdcN | ± 20 % |
Impulse sparkover voltage typ. at 100 V/µsUas | < 450 V= |
Impulse sparkover voltage typ. at 1 kV/µsUas | < 550 V= |
Nominal impulse discharge current (8/20) GDT/magazineIn | 20/5 kA |
25/7,5 | |
Nominal alternating discharge current (50 Hz) | 5 A/s |
Alternating discharge current 9 cycles, 50Hz Iwn | 100 A |
Glow voltage (average at 10 mA)Ugl | 60 V |
Arc - voltage at 1 AUbo | 15 V |
Additional Information
Max. operating currentIL | 2 A |
Insulation resistanceRisol | > 10 GΩ |
Capacitance at 1 MHzC | < 1,5 pF |
Climatic category / Relative humidity (DIN IEC 60068-1) | 40/90/21, 10%...95% rh |
Operating temperature rangeTU | -40 - +90 °C |
Dimensions (L x W x H) | 95,8 x 48,6 x 9 mm |