MP 2x2 24V-170-HF ST
Article Nr. : 971055
Plug-in module for consistently pluggable, two-parts arrester for signal lines for high frequency applications such as bus systems or video transmission. The protective module can be removed for test or maintenance purposes without changing the line impedance and therefore influencing the signal level. The base part can remain in the instalation without manipulating or removing any wire.
- Protection for 2 double or 4 single wires
- Max. frequency 170 MHz
- Rated load current: 1 A
- Protection for 2 double or 4 single wires
- Protective plug can be removed without changing the line impedance or influencing the useful signal
- Test standard: IEC 61643-21 / EN 61643-21
- Vibration test standard: DIN EN 60068-2-6, IEC 60068-2-6
- Shock test standard: DIN EN 60068-2-27, IEC 60068-2-27
- Applicable at the boundaries LPZ 0A - 1 and higher.
- Mounting on 35 mm DIN rail (EN 60715)
- Enclosure material: thermoplastic
- Housing width: 17.5 mm
IEC category | D1 / C2 / C1 / C3 |
Nominal voltage DCUN | 24 V= |
Max. continous operating voltage (DC/AC)Uc | 33/23 V |
Nominal currentIL | 1 A |
D1 lightning impulse current (10/350 µs) per lineIimp | 2,5 kA |
C2 nominal discharge current (8/20 µs) totalImax | 20 kA |
C2 nominal discharge current (8/20 µs) per lineIn | 10 kA |
Prorection level line-line at Iimp D1Up | ≤ 52 V |
Protection level line-earth at Iimp D1Up | ≤ 350 V |
Protection level line-line at 1 kV/μs C3Up | ≤ 45 V |
Additional Information
Protection level line-Pg at 1 kV/μs C3Up | ≤ 450 V |
Series resistance per line | 1,5 Ω |
Max. operating frequency (-3 dB)fG | typ. 170 MHz |
Conductor cross section (solid/stranded/AWG) | 0.2-4.0/0.2-2.5 mm² / 24-12 |
Operating temperature rangeTU | -40 - +80 °C |
Inflammability class according to UL 94 | V0 |
Degree of protection (IEC EN 60529) | IP 20 |
Enclosure material / colour | PA6 / black-yellow |
Dimension (DIN 43880) | 1 TE |
Mounting on | 35 mm DIN rail (EN 60715) |