Single-pole lightning current arrester
- Single-pole lightning current arrester
- Remote signalling contact: break contact
- Lightning current arresters type 1 (class I)
- Test standard: IEC 61643-11 / EN 61643-11
- Single-pole lightning current arrester
- EAC certification
IEC category | Type 1 / class I |
Nominal voltage ACUN | 230/400 V~ |
Max. continuous operating voltage AC (50/60 Hz) Uc | 520 V~ |
Protection level at 100% lightn. imp. sparkover voltage (1.2/50µs)Up | ≤ 4,0 kV |
Protection levelUp | ≤ 2,5 kV |
Lightning impulse current (10/350) L,N-PEIimp | 50 kA |
Follow-on current extinguishing capability at Uc (50/60 Hz)Ifi | 3,0 kA |
Short-circuit withstand capability at max. back-up fuseISCCR | 50 kAeff |
Insulation resistanceRisol | > 10 GΩ |
Response time at 1 kV/μstA | 50 ns |
Additional Information
Max. acceptable back-up fuse F2 (spur wiring) | 250 A gG |
Max. acceptable back-up fuse F1 (serial wiring) | 125 A gG |
Operating temperature rangeTU | -40 - +80 °C |
Max. conductor cross section | 50 mm² stranded/35 mm² flexible |
Max. connection torque for terminals | 4,0 Nm |
Enclosure material / colour | polycarbonate (halogen-free) UL 94-V0 / yellow |
Degree of protection (IEC EN 60529) | IP 20 |
Mounting on | 35 mm DIN rail (EN 60715) |
Max. conductor cross section FM | 1,5 mm² |
Max. locking torque FM terminals | 0,25 Nm |
Recommended conductor cross section | 25 mm² |
Dimension (DIN 43880) | 2 TE |