273002_v02.jpg
One-piece lightning current discharge arrester for signal lines with a high discharge capacity for use the at the building entry.
  • Protection of one double or two single lines.
  • Protective circuit for 2 signal lines without reference to ground potential
  • Applicable at the boundaries LPZ 0A - 1 and higher.
  • Test standard: IEC 61643-21 / EN 61643-21
  • Mounting on 35 mm DIN rail (EN 60715)
  • Degree of protection according to IEC EN 60529: IP 20
  • Space required for installation: 18 mm
  • EAC certification
IEC category D1 / C2 / C1 / C3
Nominal voltage DCUN 150 V=
Max. continuous operating voltage DCUc 170 V=
Max. continuous operating voltage AC (50/60 Hz) Uc 120 V~
Nominal currentIL 1,5 A
Leakage current at Uc DC ≤ 0.001 µA
Response timetA ≤ 50 ns
C2 nominal discharge current (8/20 µs)In 20 kA
D1 lightning impulse current (10/350 µs) totalItotal 10 kA
D1 lightning impulse current (10/350 µs) per lineIimp 5 kA
Additional Information
Protection level, residual voltage line-ground at In resp. 1 kV/µsUp ≤ 800 V
Capacitance, line-earthC < 0.005 nF
Insulation resistanceRisol > 10 GΩ
Operating temperature rangeTU -25 - +85 °C
Max. conductor cross section 2.5mm² solid or 1.5mm² flexible with sleeve
Installation dimensions (H × W × D) 18 x 87 x 58 mm
Enclosure material / colour polycarbonate (halogen-free) UL 94-V0 / yellow
Type of connection Screw terminals
Degree of protection (IEC EN 60529) IP 20
Mounting 35 mm DIN rail form C (EN 60715 )
Dimension (DIN 43880) 1 TE