PP BCD IT-NO 25/75/FM
Article Nr. : 373985
Applicable at the boundaries LPZ 0A - 1 and higher. Multi-pole SPD type 1+2+3 for 3-phase IT systems.
- Remote signalling contact: break contact
- Combined Arresters Class I+II+III (T1+T2+T3)
- Test standard: IEC 61643-11 / EN 61643-11
- High insulation resistance Risol: ? 10 G?
- Applicable at the boundaries LPZ 0A - 1 and higher.
- Preotection level ? 1.0 kV
- EAC certification
IEC category | Type 1 + 2 + 3 / class I+II+III |
Nominal voltage ACUN | 230 V~ |
Max. continuous operating voltage AC (50/60 Hz) Uc | 440 V~ |
Insulation resistanceRisol | >10 GΩ |
Protection level at 100% lightn. imp. sparkover voltage (1.2/50µs)Up | ≤ 1,0 kV |
Protection levelUp | ≤ 1,0 kV |
Response timetA | <50 ns |
Lightning impulse current (10/350 µs)Iimp | 25 (3x L-PE) kA |
Lightning impulse current (10/350 µs) totalItotal | 75 kA |
Follow-on current extinguishing capability at Uc (50/60 Hz)Ifi | 4,0 (IEC: 3.0) kA |
Additional Information
Short-circuit withstand capability at max. back-up fuse 250 A gLISCCR | 25 kAeff |
Max. acceptable backup fuse (branch wiring) | 250 A gG |
Max. acceptable backup fuse (V-type through wiring) | 125 A gG |
Operating temperature rangeTU | -40 - +80 °C |
Recommended conductor cross section | 25 mm² |
Enclosure material / colour | polycarbonate (halogen-free) UL 94-V0 / yellow |
Degree of protection (IEC EN 60529) | IP 20 |
Mounting on | 35 mm DIN rail (DIN EN 60715 ) |
Max. conductor cross section FM | 1,5 mm² |
Max. switching capacity of remote signal contact | 250 / 2 V/A |
Power supply system | 3 phase IT systems |
Dimension (DIN 43880) | 6 TE |