261212_v02.jpg
Lightning current and surge voltage protection for particularly long signal and bus lines. Thanks to the extremely low volume resistance (impedance only 0.3?) no noteworthy signal losses occur. It is a combined arrester to protect two single wires. EMC filter for data and signal lines combined with surge protection enables smooth operation of sensitive electronic equipment in rough environment.
  • Signal and data line protection with low-pass filter
  • Signal and data line protection with low-pass filter
  • Applicable at the boundaries LPZ 0A - 2 and higher
  • Very low volume resistance
  • Maximum operating current 1.5 A
  • Mounting on 35 mm DIN rail (EN 60715)
  • Degree of protection according to IEC EN 60529: IP 20
  • Space required for installation: 18 mm
  • EAC certification
IEC category D1 / C2 / C1 / C3
Nominal voltage DCUN 60 V=
Max. continuous operating voltage DCUc 64 V=
Max. continuous operating voltage AC (50/60 Hz) Uc 45 V~
Nominal currentIL 1,5 A
Longitudinal impedance (DC resistance) per wireZ 0,3 Ω
Series inductance, typ.L 56 µH
Response time fine protectiontA ≤ 2 ns
D1 lightning impulse current (10/350 µs) per lineIimp 2,5 kA
D1 lightning impulse current (10/350 µs) totalItotal 5 kA
Additional Information
C2 nominal discharge current (8/20 µs)In 10 kA
C2 nominal discharge current (8/20 µs) totalImax 20 kA
Protection level, residual voltage line-ground at In resp. 1 kV/µsUp ≤ 90 V
Leakage current at Umax DC ≤ 5 µA
Capacitance, line-earthC ≤ 1 nF
Max. operating frequency (-3 dB)fG 600 kHz
Insulation resistanceRisol > 10 GΩ
Operating temperature rangeTU -25 - +85 °C
Type of connection Screw terminals
Max. conductor cross section 2.5 mm² single-wire / 1.5 mm² flexible with sleeve
Max. connection torque for terminals 1,5 Nm
Degree of protection (IEC EN 60529) IP 20
Enclosure material / colour polycarbonate (halogen-free) UL 94-V0 / yellow
Mounting on 35 mm DIN rail (DIN EN 60715 )
Dimension (DIN 43880) 1 TE