270303_v02.jpg
EMC filter for data and signal lines combined with surge protection enables smooth operation of sensitive electronic equipment in rough environment.
  • Signal and data line protection with low-pass filter
  • Signal and data line protection with low-pass filter
  • Protective circuit for 2 signal lines without reference to ground potential
  • Applicable at the boundaries LPZ 0A - 2 and higher
  • Mounting on 35 mm DIN rail (EN 60715)
  • Degree of protection according to IEC EN 60529: IP 20
  • Space required for installation: 18 mm
  • EAC certification
IEC category D1 / C2 / C1 / C3
Nominal voltage DCUN 150 V=
Max. continuous operating voltage DCUc 160 V=
Max. continuous operating voltage AC (50/60 Hz) Uc 112 V~
Nominal currentIL 1,5 A
Leakage current at Uc DC ≤ 5 µA
Longitudinal impedance (DC resistance) per wireZ 0,3 Ω
Series inductance, typ.L 130 µH
Insulation resistanceRisol > 10 GΩ
Response timetA ≤ 2 ns
Additional Information
D1 lightning impulse current (10/350 µs) totalItotal 10 kA
D1 lightning impulse current (10/350 µs) per lineIimp 5 kA
C2 nominal discharge current (8/20 µs)In 20 kA
Protection level, residual voltage line-ground at In resp. 1 kV/µsUp ≤ 250 V
Capacitance, line-earthC < 1 nF
Max. operating frequency (-3 dB)fG 600 kHz
Operating temperature rangeTU -25 - +85 °C
Max. conductor cross section 16 mm² massiv or 6 mm² flexible with sleeve
Max. connection torque for terminals 1,5 Nm
Type of connection Screw terminals
Enclosure material / colour polycarbonate (halogen-free) UL 94-V0 / yellow
Degree of protection (IEC EN 60529) IP 20
Dimension (DIN 43880) 1 TE
Mounting on 35 mm DIN rail (EN 60715)