Fully pluggable surge protective arrester type 2 (class II) for the use between L - N wires. Complete module with 1+0 circuit.
- Remote changeover contact (FM)
- Class II (T2) Surge Arresters, pluggable
- Test standard: IEC 61643-11 / EN 61643-11
- Vibration test standard: DIN EN 60068-2-6, IEC 60068-2-6
- Shock test standard: DIN EN 60068-2-27, IEC 60068-2-27
- Mounting on 35 mm DIN rail (EN 60715)
- EAC certification
IEC category | Type 2 /class II |
Nominal voltage ACUN | 400 V~ |
Max. continuous operating voltage AC (50/60 Hz) Uc | 550 V~ |
Nominal discharge current (8/20 µs)In | 20 kA |
Max. impulse discharge current (8/20 µs)Imax | 40 kA |
Protection level at In (8/20 µs)Up | ≤ 2,5 kV |
Protection level at 5 kAUp | ≤ 1,8 kV |
Short-circuit withstand capability at max. back-up fuseISCCR | 25 kAeff |
Max. acceptable fuse or back-up fuse | 125 A gG |
Operating temperature rangeTU | -40 - +80 °C |
Additional Information
Min. conductor cross section at terminals | 1.5 mm² solid/flexible |
Max. conductor cross section | 35 mm² stranded/25 mm² flexible |
Enclosure material / colour | Thermoplastic, yellow, UL 97 V-0 |
Degree of protection (IEC EN 60529) | IP 20 |
Dimension (DIN 43880) | 1 TE |
Max. operating voltage remote contact FM | 250 V AC/125 V DC |
Max. operating current remote contact FM | 1 A AC/200 mA DC |
Max. connection torque for terminals | 3,5 Nm |
Max. locking torque FM terminals | 0,25 Nm |
Composed of: number of moduls | 1x 38 80 05 |
Power supply system | between L and N |