971051 Kopie.jpg
Plug-in module for consistently pluggable, two-parts arrester for signal lines for high frequency applications such as bus systems or video transmission. The protective module can be removed for test or maintenance purposes without changing the line impedance and therefore influencing the signal level. The base part can remain in the instalation without manipulating or removing any wire.
  • Protection for 2 double or 4 single wires
  • Max. operating frequency 70 MHz
  • Nominal current 0,5 A
  • Protective plug can be removed without changing the line impedance or influencing the useful signal
  • Test standard: IEC 61643-21 / EN 61643-21
  • Vibration test standard: DIN EN 60068-2-6, IEC 60068-2-6
  • Shock test standard: DIN EN 60068-2-27, IEC 60068-2-27
  • Applicable at the boundaries LPZ 0A - 1 and higher.
  • Mounting on 35 mm DIN rail (EN 60715)
  • Enclosure material: thermoplastic
  • Housing width: 17.5 mm
  • Protection for 2 double or 4 single wires
IEC category D1 / C2 / C1 / C3
Nominal voltage DCUN 24 V=
Max. continous operating voltage (DC/AC)Uc 33/23 V
Nominal currentIL 0,5 A
D1 lightning impulse current (10/350 µs) per lineIimp 2,5 kA
C2 nominal discharge current (8/20 µs) totalImax 20 kA
C2 nominal discharge current (8/20 µs) per lineIn 10 kA
Prorection level line-line at Iimp D1Up ≤ 52 V
Protection level line-earth at Iimp D1Up ≤ 350 V
Protection level line-line at 1 kV/μs C3Up ≤ 45 V
Additional Information
Protection level line-Pg at 1 kV/μs C3Up ≤ 450 V
Series resistance per line 1,5 Ω
Max. operating frequency (-3 dB)fG typ. 70 MHz
Conductor cross section (solid/stranded/AWG) 0.2-4.0/0.2-2.5 mm² / 24-12
Operating temperature rangeTU -40 - +80 °C
Inflammability class according to UL 94 V0
Degree of protection (IEC EN 60529) IP 20
Enclosure material / colour PA6 / black-yellow
Dimension (DIN 43880) 1 TE
Mounting on 35 mm DIN rail (EN 60715)

Accessories