They provide extremely high discharge capacity with at the same time very low protection levels and they also do not need any damageable internal or external electronic trigger. Lightning current capable and rare-gas-filled summation current spark gap for the use between N - PE wire.
- NPE lightning current arrester
- Applicable at the LPZ transition point 0A-1 respectively 0A-2 and higher
- Test standard: IEC 61643-11 / EN 61643-11
- Vibration test standard: DIN EN 60068-2-6, IEC 60068-2-6
- Shock test standard: DIN EN 60068-2-27, IEC 60068-2-27
- Enclosure material: thermoplastic with the colours yellow and black
- Mounting on 35 mm DIN rail (EN 60715)
- No leakage currents, thus, allowing installation upstream of power meters
- Optical status indication (red pin appears)
- Single modules can be replaced easily
- Remote changeover contact (FM)
- EAC certification
IEC category | Type 1 / class I |
Nominal voltage ACUN | 230 V~ |
Max. continuous operating voltage AC (50/60 Hz) Uc | 260 V~ |
Lightning impulse current (10/350 µs) totalItotal | 100 kA |
Lightning impulse current (10/350 µs) L-N/N-PE/L-PENIimp | - / 100 / - kA |
Nominal discharge current (8/20 µs) L-N/N-PE/L-PENIn | - / 100 / - kA |
Protection levelUp | ≤ 2,5 kV |
Follow-on current extinguishing capability AC N-PEIfi | 100 Aeff |
Short-circuit withstand capability at max. back-up fuseISCCR | 50 kAeff |
Max. acceptable backup fuse (branch wiring) | 250 A gG |
Additional Information
Max. acceptable backup fuse (V-type through wiring) | 125 A gG |
Operating temperature rangeTU | -40 - +80 °C |
Min. conductor cross section at terminals | 10 mm² solid/flexible |
Max. conductor cross section | 50 mm² stranded/35 mm² flexible |
Recommended conductor cross section | 25 mm² |
Max. connection torque for terminals | 4,0 Nm |
Power supply system | between N and PE |
Composed of: number of moduls | 1x 96 02 38 |
Degree of protection (IEC EN 60529) | IP 20 |
Inflammability class according to UL 94 | V0 |
Installation width | 39,8 mm |
Max. operating voltage remote contact FM | 250 V AC/125 V DC |
Max. operating current remote contact FM | 1 A AC/200 mA DC |
Max. conductor cross section FM | 1,5 mm² |
Max. locking torque FM terminals | 0,25 Nm |
Mounting on | 35 mm DIN rail (EN 60715) |