MP 2x2 GDT+170V-Ad-Ad-Pg ST
Article Nr. : 970045
Plug-in module for consistently pluggable, two-part arrester for signal circuits, which means that plugs can be pulled out in an impedance-neutral manner for testing and maintenance purposes. The base part (see accessories) remains in the installation, so there is no need to intervene in the cabling.
- Protection for 2 double or 4 single wires
- Protective plug can be removed without changing the line impedance or influencing the useful signal
- Test standard: IEC 61643-21 / EN 61643-21
- Vibration test standard: DIN EN 60068-2-6, IEC 60068-2-6
- Shock test standard: DIN EN 60068-2-27, IEC 60068-2-27
- Applicable at the boundaries LPZ 0A - 1 and higher.
- Mounting on 35 mm DIN rail (EN 60715)
- Enclosure material: thermoplastic
- Housing width: 17.5 mm
- Protection for 2 double or 4 single wires
IEC category | D1 / C2 / C1 / C3 |
Nominal voltage DCUN | 170 V= |
Max. continous operating voltage (DC/AC)Uc | 170/120 V |
Nominal currentIL | 0,5 A |
D1 lightning impulse current (10/350 µs) per lineIimp | 2,5 kA |
C2 nominal discharge current (8/20 µs) totalImax | 20 kA |
C2 nominal discharge current (8/20 µs) per lineIn | 10 kA |
Prorection level line-line at Iimp D1Up | ≤ 270 V |
Protection level line-earth at Iimp D1Up | ≤ 300 V |
Protection level line-line at 1 kV/μs C3Up | ≤ 250 V |
Additional Information
Protection level line-Pg at 1 kV/μs C3Up | ≤ 250 V |
Series resistance per line | 2,2 Ω |
Max. operating frequency (-3 dB)fG | typ. 25 MHz |
Conductor cross section (solid/stranded/AWG) | 0.2-4.0/0.2-2.5 mm² / 24-12 |
Operating temperature rangeTU | -40 - +80 °C |
Inflammability class according to UL 94 | V0 |
Degree of protection (IEC EN 60529) | IP 20 |
Enclosure material / colour | PA6 / black-yellow |
Dimension (DIN 43880) | 1 TE |
Mounting on | 35 mm DIN rail (EN 60715) |
Resistance per pathR | 2,2 ±10% Ω |