97 00 11_kl Kopie.jpg
Plug-in module for consistently pluggable, two-part arrester for signal circuits, which means that plugs can be pulled out in an impedance-neutral manner for testing and maintenance purposes. The base part (see accessories) remains in the installation, so there is no need to intervene in the cabling.
  • Protection for 2 double or 4 single wires
  • Protective plug can be removed without changing the line impedance or influencing the useful signal
  • Test standard: IEC 61643-21 / EN 61643-21
  • Vibration test standard: DIN EN 60068-2-6, IEC 60068-2-6
  • Shock test standard: DIN EN 60068-2-27, IEC 60068-2-27
  • Applicable at the boundaries LPZ 0A - 1 and higher.
  • Mounting on 35 mm DIN rail (EN 60715)
  • Enclosure material: thermoplastic
  • Housing width: 17.5 mm
  • Protection for 2 double or 4 single wires
IEC category D1 / C2 / C1 / C3
Nominal voltage DCUN 5 V=
Max. continous operating voltage (DC/AC)Uc 6/4 V
Nominal currentIL 0,5 A
D1 lightning impulse current (10/350 µs) per lineIimp 2,5 kA
C2 nominal discharge current (8/20 µs) totalImax 20 kA
C2 nominal discharge current (8/20 µs) per lineIn 10 kA
Prorection level line-line at Iimp D1Up ≤ 25 V
Protection level line-earth at Iimp D1Up ≤ 550 V
Protection level line-line at 1 kV/μs C3Up ≤ 10 V
Additional Information
Protection level line-Pg at 1 kV/μs C3Up ≤ 500 V
Series resistance per line 2,2 Ω
Max. operating frequency (-3 dB)fG typ. 1,0 MHz
Conductor cross section (solid/stranded/AWG) 0.2-4.0/0.2-2.5 mm² / 24-12
Operating temperature rangeTU -40 - +80 °C
Inflammability class according to UL 94 V0
Degree of protection (IEC EN 60529) IP 20
Enclosure material / colour PA6 / black-yellow
Dimension (DIN 43880) 1 TE
Mounting on 35 mm DIN rail (EN 60715)
Capacitance wire-wireC 6 nF pF
Resistance per pathR 2,2 ±10% Ω

Accessories