960228_CT PV-T2_2+GDT-600_v02.jpg
Suitable for insulated photovoltaic applications with system voltages up to 600 or 1000V DC. Fully pluggable and leakage-free surge protective arrester for the use in photovoltaic applications.
  • Remote changeover contact (FM)
  • SPD type 2 for DC power supplies
  • Applicable at the boundaries LPZ 0B - 1 and higher
  • Leakage current-free
  • Test standard: IEC 61643-11 / EN 61643-11
  • Vibration test standard: DIN EN 60068-2-6, IEC 60068-2-6
  • Shock test standard: DIN EN 60068-2-27, IEC 60068-2-27
  • Mounting on 35 mm DIN rail (EN 60715)
  • Space required for installation: 54 mm
  • Inflammability class according to UL 97 V0
  • EAC certification
IEC category Type 2 /class II
Open-circuit voltageUOC max. ≤ 600 V=
Max. continuous operating voltage DCUc 600 V=
Max. short-circuit currentISC max. tbd.
Nominal discharge current (8/20 µs)In 20 kA
Max. impulse discharge current (8/20 µs)Imax 40 kA
Protection Level L+-L-Up 3 kV
Protection level L+/L- -PEUp 3 kV
Operating temperature rangeTU -40 - +80 °C
Min. conductor cross section at terminals 1.5 mm² solid/flexible
Additional Information
Max. conductor cross section 35 mm² stranded/25 mm² flexible
Dimension (DIN 43880) 3 TE
Degree of protection (IEC EN 60529) IP 20
Mounting on 35 mm DIN rail (EN 60715)
Max. operating voltage remote contact FM 250 V AC/125 V DC
Max. operating current remote contact FM 1 A AC/200 mA DC
Max. locking torque FM terminals 0,25 Nm
Composed of: number of moduls 2x 96 02 46 + 1x 96 02 48

Accessories