A rare-gas-filled spark gap for the lightning protection equipotential bonding, the insulation of electrically separated parts and the bridging of insulating flanges of gas pipelines.
- Gasfilled spark gap (TS)
- AC spark-over voltage : 70 V
- DC spark-over voltage : 100 V bzw. 500 V
- DC impulse spark-over voltage (1kV/µs): 650 V
- Light. imp. current resistance (10/350µs): 100 kA
- Mounting on 35 mm DIN rail (EN 60715)
- Test standard DIN EN 62561-3:2018-02
- Degree of protection according to IEC EN 60529: IP 20
- EAC certification
IEC category | Class 1L |
Nominal DC sparkover voltage at 100 V/sUagN | 70 V= |
Nominal AC sparkover voltage (50 Hz)Uaw | 50 ±20% V |
Typical impulse sparkover voltageUas |