Surge voltage protector for equipment power supplies and installations up to 100 A and 48(60) V DC. A very low protection level allows the use as SPD type 3 (class III).
  • With potential-free remote signalling contact (Pk)
  • SPD type 2 for DC power supplies
  • High performance surge protector
  • Valve arrester SPD (leakage-current free)
  • Function control indication via LED
IEC category Type 2 /class II
Nominal voltage DCUN 48 V=
Nominal voltage ACUN 34 V~
Max. continuous operating voltage DCUc 60 V=
Max. continuous operating voltage AC (50/60 Hz) Uc 42 V~
Nominal currentIL 100 A
Protection level at 1 kV/µs (1, 2-PE)Up ≤ 0,2 kV
Protection level at In (1, 2-PE)Up ≤ 0.3 kV
Response timetA < 25 ns
Nominal discharge current (8/20 µs)In 15 kA
Additional Information
Max. impulse discharge current (8/20 µs)Imax 30 kA
Max. allowed fuse or back-up fuse 125 A gG
Operating temperature rangeTU -40 - +80 °C
Max. conductor cross section 50 mm² stranded/35 mm² flexible
Recommended conductor cross section 25 mm²
Max. connection torque for terminals 4,0 Nm
Enclosure material / colour polycarbonate (halogen-free) UL 94-V0 / yellow
Degree of protection (IEC EN 60529) IP 20
Mounting on 35 mm DIN rail (DIN EN 60715 )
FM contact / contact type break contact
Switching capacity FM 250 V/2 A
Max. conductor cross section Pk 1,5 mm²