EP D TN 230V/16A/FM
Article Nr. : 380563
The SPD is applicable at the transition 2-3 according to the lightning protection zones concept. Compact 2-pole surge arrester type 3 (class III) for the use in TN systems.
- Remote signalling contact: break contact
- Possible with parallel or spur wiring for >16 A
- Surge voltage protector (class III T3 )
- Test standard: IEC 61643-11 / EN 61643-11
- Line function and equipment control by LED
- Leackage current free
- Practical compact housing with minimum space requirement
- EAC certification
IEC category | Type 3 / class III |
Nominal voltage ACUN | 230 V~ |
Nominal voltage DCUN | 230 V= |
Max. continuous operating voltage AC (50/60 Hz) Uc | 255 V~ |
Max. continuous operating voltage DCUc | 255 V= |
Rated load currentIL | 16 A |
Protection level L-NUp | ≤ 1,0 kV |
Protection level L/N-PEUp | ≤ 1,5 kV |
Combined surgeUoc | 4 kV |
Response time L-N/L,N-PE | ≤ 25/≤ 100 ns |
Additional Information
Nominal impulse discharge current (10 x 8/20 µs)In | 5 kA |
Max. impulse discharge current (8/20 µs)Imax | 8 kA |
Max. allowed fuse or back-up fuse | 16 A gG |
Operating temperature rangeTU | -40 - +80 °C |
Min. conductor cross section at terminals | 1.5 mm² single-wire / 1.0 mm² flexible with sleeve |
Max. conductor cross section | 2.5 mm² single-wire / 1.5 mm² flexible with sleeve |
Max. connection torque for terminals | 1,5 Nm |
Enclosure material / colour | polycarbonate (halogen-free) UL 94-V0 / yellow |
Degree of protection (IEC EN 60529) | IP 20 |
Mounting on | 35 mm DIN rail (EN 60715) |
FM contact / contact type | break contact |
Switching capacity FM | 250 V/2 A |
Max. conductor cross section FM | 1,5 mm² |
Max. locking torque FM terminals | 1,5 Nm |
Power supply system | 1 phase TN systems |