IP B TNC 25/75/FM
Article Nr. : 381217
The arresters can be installed at the transition 0A to 1 according to the lightning protection zones concept. Multi-pole lightning current arrester for 3-phase TN-C systems.
- Lightning current arresters type 1 (class I)
- Test standard: IEC 61643-11 / EN 61643-11
- Rare-gas-filled spark gap, hermetically sealed
- High insulation resistance
- Degree of protection according to IEC EN 60529: IP 20
- Inflammability class according to UL 94 V0
- Mounting on 35 mm DIN rail (EN 60715)
- EAC certification
- All-in-one protection unit, ready for connection
- Remote signalling contact: break contact
- Switching capacity FM: 205 V /2 A
- Max. conductor cross section FM: 1.5 mm²
IEC category | Type 1 / class I |
Nominal voltage ACUN | 230/400 V~ |
Max. continuous operating voltage AC (50/60 Hz) Uc | 255 V~ |
Insulation resistanceRisol | >10 GΩ |
Protection level at 100% lightn. imp. sparkover voltage (1.2/50µs)Up | ≤ 4,0 kV |
Protection levelUp | ≤ 4,0 kV |
Response timetA | <50 ns |
Lightning impulse current (10/350 µs) totalItotal | 75 kA |
Lightning impulse current (10/350 µs) L-N/N-PE/L-PENIimp | - / - / 25 kA |
Short-circuit withstand capability at max. back-up fuseISCCR | 50 kAeff |
Additional Information
Max. acceptable back-up fuse F2 (spur wiring) | 160 A gG |
Max. acceptable back-up fuse F1 (serial wiring) | 125 A gG |
Operating temperature rangeTU | -40 - +80 °C |
Max. conductor cross section | stranded 50/fine stranded 35 mm² |
Recommended conductor cross section | 25 mm² |
Max. connection torque for terminals | 4,0 Nm |
Enclosure material / colour | polycarbonate (halogen-free) UL 94-V0 / yellow |
Switching capacity FM | 250 V/2 A |
Max. conductor cross section FM | 1,5 mm² |
Max. locking torque FM terminals | 0,25 Nm |
Power supply system | 3 phase TNC systems |
Dimension (DIN 43880) | 6 TE |