381140_IP B TNC 60_100_v03.jpg
The arresters can be installed at the transition 0A to 1 according to the lightning protection zones concept. Multi-pole lightning current arrester for 3-phase TN-C systems.
  • Lightning current arresters type 1 (class I)
  • Test standard: IEC 61643-11 / EN 61643-11
  • Rare-gas-filled spark gap, hermetically sealed
  • High insulation resistance
  • Degree of protection according to IEC EN 60529: IP 20
  • Inflammability class according to UL 94 V0
  • Mounting on 35 mm DIN rail (EN 60715)
  • EAC certification
  • All-in-one protection unit, ready for connection
  • Remote signalling contact: break contact
  • Switching capacity FM: 205 V /2 A
  • Max. conductor cross section FM: 1.5 mm²
IEC category Type 1 / class I
Nominal voltage ACUN 230/400 V~
Max. continuous operating voltage AC (50/60 Hz) Uc 255 V~
Insulation resistanceRisol > 10 GΩ
Protection level at 100% lightn. imp. sparkover voltage (1.2/50µs)Up ≤ 4,0 kV
Protection levelUp ≤ 4,0 kV
Response timetA <50 ns
Lightning impulse current (10/350 µs) totalItotal 100 kA
Lightning impulse current (10/350 µs) L-N/N-PE/L-PENIimp - / - / 60 kA
Short-circuit withstand capability at max. back-up fuseISCCR 50 kAeff
Additional Information
Max. acceptable back-up fuse F2 (spur wiring) 160 A gG
Max. acceptable back-up fuse F1 (serial wiring) 125 A gG
Operating temperature rangeTU -40 - +80 °C
Max. conductor cross section stranded 50/fine stranded 35 mm²
Recommended conductor cross section 25 mm²
Max. connection torque for terminals 4,0 Nm
Enclosure material / colour polycarbonate (halogen-free) UL 94-V0 / yellow
Switching capacity FM 250 V/2 A
Max. conductor cross section FM 1,5 mm²
Max. locking torque FM terminals 0,25 Nm
Power supply system 3 phase TNC systems
Dimension (DIN 43880) 6 TE