Multi-pole lightning current arrester (class I) for 2-phase TT systems.
  • Remote signalling contact: break contact
  • Lightning current arresters type 1 (class I)
  • Test standard: IEC 61643-11 / EN 61643-11
  • EAC certification
IEC category Type 1 / class I
Nominal voltage ACUN 100/200 bzw. 110/220 V~
Max. continuous operating voltage AC (50/60 Hz) Uc 255 V~
Insulation resistanceRisol >10 GΩ
Protection level at 100% lightn. imp. sparkover voltage (1.2/50µs)Up ≤ 4,0 kV
Protection levelUp ≤ 4,0 kV
Response timetA <50 ns
Lightning impulse current (10/350 µs) totalItotal 100 kA
Lightning impulse current (10/350 µs) L-N/N-PE/L-PENIimp 50 / 100 / - kA
Nominal discharge current (8/20 µs)In 100 kA
Additional Information
Max. impulse discharge current (8/20 µs)Imax 140 kA
Follow-on current extinguishing capability at Uc (50/60 Hz)Ifi 4 kA
Short-circuit withstand capability at max. back-up fuseISCCR 50 kAeff
Max. acceptable back-up fuse F2 (spur wiring) 250 A gG
Max. acceptable back-up fuse F1 (serial wiring) 125 A gG
Operating temperature rangeTU -40 - +80 °C
Max. conductor cross section 50 mm² stranded/35 mm² flexible
Recommended conductor cross section 25 mm²
Max. connection torque for terminals 4,0 Nm
Enclosure material / colour polycarbonate (halogen-free) UL 94-V0 / yellow
Switching capacity FM 250 V/2 A
Max. conductor cross section FM 1,5 mm²
Max. locking torque FM terminals 0,25 Nm
Power supply system 2 phase TT system
Dimension (DIN 43880) 6 TE