Lightning current discharge arrester (class I) with rare-gas-filled spark gap for the use in three-phase TNC systems. Applicable at the boundaries LPZ 0A - 1 and higher.
- Remote signalling contact: break contact
- Lightning current arresters type 1 (class I)
- Test standard: IEC 61643-11 / EN 61643-11
- Applicable at the boundaries LPZ 0A - 1 and higher.
- High quenching of follow-on short-circuit currents
- High TOV resistance
- No leakage currents, thus, allowing installation upstream of power meters
- Degree of protection according to IEC EN 60529: IP 20
- Mounting on 35 mm DIN rail (EN 60715)
- EAC certification
IEC category | Type 1 / class I |
Nominal voltage ACUN | 400/690 V~ |
Max. continuous operating voltage AC (50/60 Hz) Uc | 440 V~ |
Insulation resistanceRisol | >10 GΩ |
Protection level at 100% lightn. imp. sparkover voltage (1.2/50µs)Up | ≤ 4,0 kV |
Protection levelUp | ≤ 4,0 kV |
Response timetA | <50 ns |
Lightning impulse current (10/350 µs) totalItotal | 75 kA |
Lightning impulse current (10/350 µs) L-N/N-PE/L-PENIimp | - / - / 25 kA |
Follow-on current extinguishing capability at Uc (50/60 Hz)Ifi | 4 kA |
Additional Information
Short-circuit withstand capability at max. back-up fuseISCCR | 50 kAeff |
Max. acceptable back-up fuse F2 (spur wiring) | 63 A gG |
Max. acceptable back-up fuse F1 (serial wiring) | 63 A gG |
Operating temperature rangeTU | -40 - +80 °C |
Max. conductor cross section | 50 mm² stranded/35 mm² flexible |
Recommended conductor cross section | 25 mm² |
Max. connection torque for terminals | 4,0 Nm |
Enclosure material / colour | polycarbonate (halogen-free) UL 94-V0 / yellow |
Switching capacity FM | 250 V/2 A |
Max. conductor cross section FM | 1,5 mm² |
Max. locking torque FM terminals | 0,25 Nm |
Power supply system | 3 phase TNC systems |
Dimension (DIN 43880) | 6 TE |