PP BCD TT1+1 25/100/FM-350
Article Nr. : 385090
Combined arrester for the protection of low-voltage consumers’ installations in industry, business and residential areas against transient surges caused by lightning (LEMP) or switching actions in the network (SEMP). Combined two-pole arrester for 1-phase TT systems.
- Combined Arresters Class I+II+III (T1+T2+T3)
- Test standard: IEC 61643-11 / EN 61643-11
- Rare-gas-filled spark gap, hermetically sealed
- No leakage currents, thus, allowing installation upstream of power meters
- Mounting on 35 mm DIN rail (EN 60715)
- EAC certification
IEC category | Type 1 + 2 + 3 / class I+II+III |
Nominal voltage ACUN | 230/400 V~ |
Max. continuous operating voltage AC (50/60 Hz) Uc | 350 V~ |
Insulation resistanceRisol | > 10 GΩ |
Protection level at 100% lightn. imp. sparkover voltage (1.2/50µs)Up | ≤ 1,0 kV |
Protection levelUp | ≤ 1,0 kV |
Response timetA | < 50 ns |
Lightning impulse current (10/350 µs) totalItotal | 100 kA |
Lightning impulse current (10/350 µs) L-N/N-PE/L-PENIimp | 25 / 100 / - kA |
Follow-on current extinguishing capability at Uc (50/60 Hz)Ifi | 4,0 kA |
Additional Information
Short-circuit withstand capability at max. back-up fuseISCCR | 50 kAeff |
Max. acceptable back-up fuse F2 (spur wiring) | 250 A gG |
Max. acceptable back-up fuse F1 (serial wiring) | 125 A gG |
Operating temperature rangeTU | -40 - +80 °C |
Max. conductor cross section | stranded 50/fine stranded 35 mm² |
Recommended conductor cross section | 25 mm² |
Max. connection torque for terminals | 4,0 Nm |
Enclosure material / colour | polycarbonate (halogen-free) UL 94-V0 / yellow |
Degree of protection (IEC EN 60529) | IP 20 |
Mounting on | 35 mm DIN rail (EN 60715) |
FM contact / contact type | break contact |
Switching capacity FM | 250 V/2 A |
Max. conductor cross section FM | 1,5 mm² |
Max. locking torque FM terminals | 0,25 Nm |
Power supply system | 1 phase TT systems |
Dimension (DIN 43880) | 4 TE |