381134_PP_BCD_TT1+1 25_100_v03.jpg
Combined arrester for the protection of low-voltage consumers’ installations in industry, business and residential areas against transient surges caused by lightning (LEMP) or switching actions in the network (SEMP). Combined two-pole arrester for 1-phase TT systems.
  • Combined Arresters Class I+II+III (T1+T2+T3)
  • Test standard: IEC 61643-11 / EN 61643-11
  • Rare-gas-filled spark gap, hermetically sealed
  • No leakage currents, thus, allowing installation upstream of power meters
  • Mounting on 35 mm DIN rail (EN 60715)
  • EAC certification
IEC category Type 1 + 2 + 3 / class I+II+III
Nominal voltage ACUN 230/400 V~
Max. continuous operating voltage AC (50/60 Hz) Uc 255 V~
Insulation resistanceRisol > 10 GΩ
Protection level at 100% lightn. imp. sparkover voltage (1.2/50µs)Up ≤ 1,0 kV
Protection levelUp ≤ 1,0 kV
Response timetA < 50 ns
Lightning impulse current (10/350 µs) totalItotal 100 kA
Lightning impulse current (10/350 µs) L-N/N-PE/L-PENIimp 25 / 100 / - kA
Follow-on current extinguishing capability at Uc (50/60 Hz)Ifi 4,0 kA
Additional Information
Short-circuit withstand capability at max. back-up fuseISCCR 50 kAeff
Max. acceptable back-up fuse F2 (spur wiring) 250 A gG
Max. acceptable back-up fuse F1 (serial wiring) 125 A gG
Operating temperature rangeTU -40 - +80 °C
Max. conductor cross section stranded 50/fine stranded 35 mm²
Recommended conductor cross section 25 mm²
Max. connection torque for terminals 4,0 Nm
Enclosure material / colour polycarbonate (halogen-free) UL 94-V0 / yellow
Degree of protection (IEC EN 60529) IP 20
Mounting on 35 mm DIN rail (EN 60715)
FM contact / contact type break contact
Switching capacity FM 250 V/2 A
Max. conductor cross section FM 1,5 mm²
Max. locking torque FM terminals 0,25 Nm
Power supply system 1 phase TT systems
Dimension (DIN 43880) 4 TE

Related Products