374520_PP_B_25_760_v02.jpg
Lightning current arrester (class I) for wind energy applications for lightning protection equipotential bonding in 690 V IT systems.
  • Remote signalling contact: break contact
  • Protection of Wind Energy Systems
  • Test standard: IEC 61643-11 / EN 61643-11
  • New developed ceramic isolating spark gap
  • EAC certification
IEC category Type 1 / class I
Nominal voltage ACUN 690 V~
Max. continuous operating voltage AC (50/60 Hz) Uc 760 V~
Insulation resistanceRisol > 10 GΩ
Protection levelUp 4,0 kV
Response timetA 100 ns
Lightning impulse current (10/350 µs) totalItotal 25 kA
Lightning impulse current (10/350 µs) L-N/N-PE/L-PENIimp 25 / - / - kA
Follow-on current extinguishing capability at Uc (50/60 Hz)Ifi 10 kA
Max. acceptable back-up fuse F2 (spur wiring) 250 A gG
Additional Information
Max. acceptable back-up fuse F1 (serial wiring) 125 A gG
Operating temperature rangeTU -40 - +80 °C
Max. conductor cross section 50 mm² stranded/35 mm² flexible
Recommended conductor cross section 25 mm²
Max. connection torque for terminals 4,0 Nm
Enclosure material / colour polyamide PA 6 30SV, UL94 VO / yellow
Degree of protection (IEC EN 60529) IP 20
Mounting on 35 mm DIN rail (EN 60715)
FM contact / contact type break contact
Switching capacity FM 250 V/2 A
Max. conductor cross section FM 1,5 mm²
Max. locking torque FM terminals 0,25 Nm
Power supply system between L and PE
Dimension (DIN 43880) 2 TE