Multi-pole lightning current arrester (class I) for 2-phase TT systems. They provide extremely high discharge capacity with at the same time very low protection levels and they also do not need any damageable internal or external electronic trigger.
- Lightning current arresters type 1 (class I)
- Applicable at the boundaries LPZ 0A - 1
- Test standard: IEC 61643-11 / EN 61643-11
- Shock test standard: DIN EN 60068-2-27, IEC 60068-2-27
- Vibration test standard: DIN EN 60068-2-6, IEC 60068-2-6
- No leakage currents, thus, allowing installation upstream of power meters
- Mounting on 35 mm DIN rail (EN 60715)
- Enclosure material: thermoplastic with the colours yellow and black
- Optical status indication (red pin appears)
- Single modules can be replaced easily
- Remote changeover contact (FM)
- EAC certification
IEC category | Type 1 / class I |
Nominal voltage ACUN | 230/400 V~ |
Max. continuous operating voltage AC (50/60 Hz) Uc | 350 V~ |
Lightning impulse current (10/350 µs) totalItotal | 100 kA |
Lightning impulse current (10/350 µs) L-N/N-PE/L-PENIimp | 25 / 100 / - kA |
Nominal discharge current (8/20 µs) L-N/N-PE/L-PENIn | 25 / 100 / - kA |
Protection levelUp | ≤ 2,5 kV |
Follow-on current extinguishing capability AC L-N (260 V AC) Ifi | 10 kAeff |
Short-circuit withstand capability at max. back-up fuseISCCR | 50 kAeff |
Max. acceptable backup fuse (branch wiring) | 250 A gG |
Additional Information
Max. acceptable backup fuse (V-type through wiring) | 125 A gG |
Operating temperature rangeTU | -40 - +80 °C |
Min. conductor cross section at terminals | 10 mm² solid/flexible |
Max. conductor cross section | 50 mm² stranded/35 mm² flexible |
Recommended conductor cross section | 25 mm² |
Max. connection torque for terminals | 4,0 Nm |
Degree of protection (IEC EN 60529) | IP 20 |
Power supply system | 2 phase TT system |
Composed of: number of moduls | 2x 96 02 37 / 1x 96 02 38 |
Installation width | 113,5 mm |
Follow-on current extinguishing capability AC N-PEIfi | 100 Aeff |
Max. operating voltage remote contact FM | 1 A AC/200 mA DC |
Max. operating current remote contact FM | 250 V AC/125 V DC |
Max. conductor cross section FM | 1,5 mm² |
Max. locking torque FM terminals | 0,25 Nm |
Inflammability class according to UL 94 | V0 |