Lightning current discharge arrester (class I) with rare-gas-filled spark gap for the use in three-phase TT and TN-S systems. They provide extremely high discharge capacity with at the same time very low protection levels and they also do not need any damageable internal or external electronic trigger.
- Lightning current arresters type 1 (class I)
- Applicable at the boundaries LPZ 0A - 1
- Test standard: IEC 61643-11 / EN 61643-11
- Vibration test standard: DIN EN 60068-2-6, IEC 60068-2-6
- Shock test standard: DIN EN 60068-2-27, IEC 60068-2-27
- Mounting on 35 mm DIN rail (EN 60715)
- Enclosure material: thermoplastic with the colours yellow and black
- No leakage currents, thus, allowing installation upstream of power meters
- Optical status indication (red pin appears)
- Single modules can be replaced easily
- Remote changeover contact (FM)
- EAC certification
IEC category | Type 1 / class I |
Nominal voltage ACUN | 230/400 V~ |
Max. continuous operating voltage AC (50/60 Hz) Uc | 350 V~ |
Lightning impulse current (10/350 µs) totalItotal | 100 kA |
Lightning impulse current (10/350 µs) L-N/N-PE/L-PENIimp | 25 / 100 / - kA |
Nominal discharge current (8/20 µs) L-N/N-PE/L-PENIn | 25 / 100 / - kA |
Protection levelUp | ≤ 2,5 kV |
Follow-on current extinguishing capability AC L-N (260 V AC) Ifi | 10 kAeff |
Follow-on current extinguishing capability AC N-PEIfi | 100 Aeff |
Short-circuit withstand capability at max. back-up fuseISCCR | 50 kAeff |
Additional Information
Max. acceptable backup fuse (branch wiring) | 250 A gG |
Max. acceptable backup fuse (V-type through wiring) | 125 A gG |
Operating temperature rangeTU | -40 - +80 °C |
Min. conductor cross section at terminals | 10 mm² solid/flexible |
Max. conductor cross section | 50 mm² stranded/35 mm² flexible |
Recommended conductor cross section | 25 mm² |
Max. connection torque for terminals | 4,0 Nm |
Degree of protection (IEC EN 60529) | IP 20 |
Power supply system | 3 phase TNS and TT systems |
Composed of: number of moduls | 3x 96 02 37 + 1x 96 02 38 |
Installation width | 147,2 mm |
Max. conductor cross section FM | 1,5 mm² |
Max. operating voltage remote contact FM | 250 V AC/125 V DC |
Max. operating current remote contact FM | 1 A AC/200 mA DC |
Max. locking torque FM terminals | 0,25 Nm |
Inflammability class according to UL 94 | V0 |