240140_2012.jpg
Pluggable surge arrester for telecommunication lines with 10 pair of wires (DA) for LSA (IDC) disconnection modules. Coarse and fine protection (high speed TVS-diodes) for measuring and control systems
  • Pluggable surge voltage protection modules for 10-wire pairs for LSA (IDC) disconnection modules
IEC category C2 / C1
Nominal voltage DCUN 110 V=
Max. continuous operating voltage DCUc 180 V=
Max. continuous operating voltage AC (50/60 Hz) Uc 180 V~
Residual voltage at 1 kV/μsUres ≤ 250 V
Nom. operating current at 25°CIL 145 mA
C2 nominal discharge current (8/20 µs)In 10x 5 kA
C2 nominal discharge current (8/20 µs) totalImax 10 kA
Protection level at In (8/20 µs)Up 220 V
Response timetA ≤ 1 ns
Additional Information
Capacitance, line-earthC < 0,1 nF
Series impedance per line at 25°CR 9 - 11 Ω
Max. transmission frequencyfg ≤ 2 MHz
Operating temperature rangeTU -40 - +80 °C
Thermal overload protection thermical fail-safe (short-circuit spring) and PTC
Enclosure material / colour Thermoplastic: grey
Dimensions (L x W x H) 110 x 22 x 72 mm