CT-T1+2/1+0-350-FM
Article Nr. : 960011
They provide extremely high discharge capacity with at the same time very low protection levels and they also do not need any damageable internal or external electronic trigger. Lightning current discharge arrester with rare-gas-filled spark gap and very low protection level < 1.5 kV for the use between L - N wire.
- Combined Arresters Type 1+2 (Class I+II)
- Applicable at the boundaries LPZ 0A - 2
- Test standard: IEC 61643-11 / EN 61643-11
- Mounting on 35 mm DIN rail (EN 60715)
- Enclosure material: thermoplastic with the colours yellow and black
- No leakage currents, thus, allowing installation upstream of power meters
- Vibration test standard: DIN EN 60068-2-6, IEC 60068-2-6
- Shock test standard: DIN EN 60068-2-27, IEC 60068-2-27
- Optical status indication (red pin appears)
- Single modules can be replaced easily
- Remote changeover contact (FM)
- EAC certification
IEC category | Type 1 + 2 / class I+II |
Nominal voltage ACUN | 230/400 V~ |
Max. continuous operating voltage AC (50/60 Hz) Uc | 350 V~ |
Lightning impulse current (10/350 µs) totalItotal | 25 kA |
Lightning impulse current (10/350 µs) L-N/N-PE/L-PENIimp | 25 / - / - kA |
Nominal discharge current (8/20 µs) L-N/N-PE/L-PENIn | 25 / - / 25 kA |
Protection levelUp | ≤ 1,5 kV |
Follow-on current extinguishing capability AC L-N (260 V AC) Ifi | 4 kAeff |
Short-circuit withstand capability at max. back-up fuseISCCR | 50 kAeff |
Max. acceptable backup fuse (branch wiring) | 250 A gG |
Additional Information
Max. acceptable backup fuse (V-type through wiring) | 125 A gG |
Operating temperature rangeTU | -40 - +80 °C |
Min. conductor cross section at terminals | 10 mm² solid/flexible |
Max. conductor cross section | 50 mm² stranded/35 mm² flexible |
Recommended conductor cross section | 25 mm² |
Max. connection torque for terminals | 4,0 Nm |
Power supply system | between L and N |
Composed of: number of moduls | 1x 96 02 36 |
Degree of protection (IEC EN 60529) | IP 20 |
Inflammability class according to UL 94 | V0 |
Installation width | 39,8 mm |
Max. operating voltage remote contact FM | 250 V AC/125 V DC |
Max. operating current remote contact FM | 1 A AC/200 mA DC |
Max. locking torque FM terminals | 0,25 Nm |
Max. conductor cross section FM | 1,5 mm² |
Mounting on | 35 mm DIN rail (EN 60715) |