With an active cathodic corrosion protection the installation is permanently protected against the electrochemical process of corrosion. For that matter a grid supplied rectifier is inserted between the installation (e.g. a pipeline) and an anode that serves as earth electrode. By connecting two or three PLPro units in parallel the overall current can be elevated up to 80 respectively 120 A.
  • AC discharge current: 40 or 80 A
  • Several PLPro devices can be connected in parallel to raise the total discharge current
  • Maintenance-free
  • No disturbance of search signals
  • Monitoring of discharge current with integrated current transformer possible
  • Integrated lightning and surge current protection up to 100 kA (10/350 µs)
  • Safety switch for discharging the capacitors
Rated voltage (P-E)Umax 25 V=
Max. continuous diverting current 50Hz (P-E)IA 40 A~
Short-time discharge current for 1s/50Hz (P-E)Imax 400 A~
Leakage current (P-E) ≤ 1 mA
Nominal discharge current (8/20 µs) (P-E)In 10x 100 kA
Lightning impulse current (10/350 µs)Iimp 100 kA
Capacitance condensatorsC 2x 100.000 µF
Operating temperature rangeTU -40 - +80 °C
Terminals (P/E) min. 16 / max. 150 mm²
Current transformer 100:1 A
Additional Information
Terminals (current transformer i1, i2) 25 mm²
Mounting wall mounting
Dimensions (L x W x H) 400 x 300 x 132 mm
Degree of protection (IEC EN 60529) IP 65