240049_2012.jpg
Lightning and surge protection for telephone installations. Pluggable module for LSA (IDC) disconnection modules. Surge voltage protection connector for 1 DA with fail-safe contact (only coarse protection) for analogue, ISDN and ADSL lines.
IEC category C2 / C1
Nominal voltage DCUN 110 V=
Max. continuous operating voltage DCUc 180 V=
Max. continuous operating voltage AC (50/60 Hz) Uc 127 V~
Nominal DC sparkover voltage at 100 V/sUagN 230 ±20% V=
C3 protection level at 1 kV/μs (line-PG)Up ≤ 600 V
Nom. operating current at 25°CIL 1000 mA
C2 nominal discharge current (8/20 µs)In 5 kA
C2 nominal discharge current (8/20 µs) totalImax 10 kA
Alternating discharge current 9 cycles, 50Hz Iwn 40 A
Additional Information
Response time (line-line)/(line-earth)tA ≤ 50 ns
Self-capacitance line-earth at 1 MHzC ≤ 5 pF
Max. transmission frequencyfg >30 MHz
Thermal overload protection thermical fail-safe (short-circuit spring)
Operating temperature rangeTU -25 - +60 °C
Earthing (Grounding) by via grounding bar and isolation unit on LSA backmount frame
Enclosure material / colour self-extinguishing thermoplastic (POCAN) UL 94 V0, grey