Surge voltage and surge current protection for communication and data transmission lines. Protection connector (1DA) with surge current protection via PTC thermistors, for analogue, ISDN and ADSL lines. Integrated coarse and fine protection and fail-safe contact. Earthing by a grounding bar, which is connected to the backmount frame via the disconnection module.
IEC category | C2 / C1 |
Nominal voltage DCUN | 110 V= |
Max. continuous operating voltage DCUc | 180 V= |
Nom. operating current at 25°CIL | 150 mA |
C2 nominal discharge current (8/20 µs)In | 5 kA |
C2 nominal discharge current (8/20 µs) totalImax | 10 kA |
Protection level at In (8/20 µs)Up | ≤ 300 V |
Residual voltage at 1 kV/μs (line-PG, line-line)Ures | ≤ 300 V |
Response timetA | ≤ 5 ns |
Transversal CapacitanceC | ≤ 60 pF |
Additional Information
Series impedance per line at 25°CR | 9 - 11 Ω |
Max. transmission frequencyfg | > 20 MHz |
Thermal overload protection | thermical fail-safe (short-circuit spring) and PTC |
Operating temperature rangeTU | -25 - +60 °C |
Earthing (Grounding) by | via grounding bar and isolation unit on LSA backmount frame |
Enclosure material / colour | self-extinguishing thermoplastic (POCAN) UL 94 V0, grey |