Surge protection device for data and signal lines in measuring systems and automatic control devices. Surge voltage protection connector for 1 DA, withsurge current protection via PTC thermistors and fail-safe contact for LSA (IDC) disconnection modules.
- Coarse and fine protection
- Surge current protection via PTC thermistors
- Suitable for DC and AC application
IEC category | C2 / C1 |
Max. continuous operating voltage DCUc | 12 V= |
Nominal voltage ACUN | 8 V~ |
Max. continuous operating voltage AC (50/60 Hz) Uc | 10 V~ |
Nom. operating current at 25°CIL | 150 mA |
C2 nominal discharge current (8/20 µs)In | 5 kA |
C2 nominal discharge current (8/20 µs) totalImax | 10 kA |
Protection level at In (line-PG)Up | ≤ 28 V |
Residual voltage at 1 kV/μs (line-PG)Ures | ≤ 22 V |
Response timetA | ≤ 1 ns |
Additional Information
Thermal overload protection | thermical fail-safe (short-circuit spring) and PTC |
Capacitance, line-earthC | ≤ 2,5 nF |
Series impedance per line at 25°CR | 9 - 11 Ω |
Max. transmission frequencyfg | > 1,0 MHz |
Operating temperature rangeTU | -25 - +60 °C |
Earthing (Grounding) by | via grounding bar and isolation unit on LSA backmount frame |
Enclosure material / colour | self-extinguishing thermoplastic (POCAN) UL 94 V0, grey |